Beipackinformation 1Operating Instructions15Notice d’utilisation 27AnalogsignaltrennerWAVEANALOG PRO RTDaus der WAVESERIESRT Nr. 406042
234. MountingThe analogue signal isolators are mounted on standard TS 35 rails. 5. Electrical connectionWarning! For applications with high isolation
2492,49038111,473,417,5mmCross-connections for power supplyGND24 Vdc6. Dimensions
257. Accessories (cross-connection)Designation Cat. No.ZQV 2,5 N/2 yellow 169380ZQV 2,5 N/2 red 171790ZQV 2,5 N/2 blue 171799ZQV 2,5 N/2 black 171808C
26Weidmüller Interface GmbH & Co. Postfach 30 30D-32720 DetmoldTel. (0 52 31) 14-0Fax (0 52 31) 14-20 83
15Analogue Signal IsolatorsWAVESERIESWAVEANALOGUE PRO RTDMODEL Order NumberScrew terminal connectionWAS5 PRO RTD 8560700000Tension clamp connectionWAZ
161. General instructionsWarning! The analogue signal isolators of the WAVEANALOGUE PRO seriesmay only be installed by qualified personnel. Be sure no
173. Configuration3.1 EquipmentA screwdriver with a width of 2.5 mm is required to adjust the unit and toconnect the wires to the terminals.3.2 Openin
18Selecting the inputsSW1Input 1 2 3PT100 2-wire 1 1 1PT100 3-wire 0 1 1PT100 4-wire 1 0 1R 2-wire 0 0 1NI100 2-wire 1 1 0NI100 3-wire 0 1 0NI100 4-wi
19SW1 min Rmin Potimin 4567–100º C 100 Ω 0100–150 °C 150 Ω 0011–200 °C 200 Ω 0010Special range 0000Activating the manual fine adjustmentSW1manual cal
20Selecting the measuring rangeSW2T R Poti 1234540K 20 Ω 20% 1111150K 25 Ω 25% 1111060K 30 Ω 30% 1110170K 35 Ω 35% 1110080K 40 Ω 40% 1101190K 45 Ω 45%
21SW2T R Poti 12345550K 275 Ω – 00111600K 300 Ω – 00110650 K 325 Ω – 00101700K 350 Ω – 00100750K 375 Ω – 00011800K 400 Ω – 00010850K 425 Ω – 00001900K
Selecting the step response timeSW2Step response 8slow 1fast 01 = on0 = off3.4 Terminal assignment of the sensorsTerminal assignment for 2-, 3-, 4-wir