SL-MOD-GW Modbus/TCP gateway
Quick start
IGSLMODGW-1002
This document is a reference guide only and must be used
in conjunction with the SL-MOD-GW User manual.
SAFETY PRECAUTIONS
ELECTRICAL HAZARD
This equipment must be installed and serviced only by
qualified personnel. Such work should be performed only
after reading the SL-MOD-GW User manual in its entirety.
Before performing visual inspections, tests, or
maintenance on this equipment, disconnect all sources of
electric power. Assume that all circuits are live until they
have been completely de-energized, tested, and tagged.
Pay particular attention to the design of the power system.
Consider all sources of power, including the possibility of
backfeeding.
Apply appropriate personal protective equipment and
follow safe electrical practices.
Turn off all power supplying the equipment in which the
SL-MOD-GW is to be installed before installing, wiring or
removing the SL-MOD-GW.
Always use a properly rated voltage sensing device to
confirm that power is off.
The successful operation of this equipment depends upon
proper handling, installation, and operation. Neglecting
fundamental installation requirements may lead to
personal injury as well as damage to electrical equipment
or other property.
Failure to follow these instructions could result in death
or serious injury!
INTRODUCTION
Package Contents
SL-MOD-GW unit
Quick start
2-pin terminal block plug
6-pin terminal block plug
Documentation and Additional Resources
This Quick start must be used in conjunction with the SL-MOD-GW
User manual.
Quick start checklist
Obtain a copy of the SL-MOD-GW User manual and read it properly
and in its entirety.
Mount the unit.
Connect the power. Do not connect yet serial ports.
Configure the Ethernet communications settings with a web browser
(using an Ethernet crossover cable) or with a terminal program like
HyperTerminal (using a null modem cable)
Configure the serial line communication settings.
Configure the operational aspects of the device.
Wire serial line interfaces.
DESCRIPTION
TOP VIEW
BOTTOM VIEW
FRONT VIEW
Clear front cover
RS-232 connector
Ethernet connector
DIN rail clip
Power LED
Ethernet link LED
Status 1 LED
Status 2 LED
Power terminals
RS-485/RS-422 terminals
INSTALLATION
Regulatory notes
1. The SL-MOD-GW is suitable for use in non-hazardous
locations only.
2. The SL-MOD-GW is not authorized for use in life support
devices or systems.
3. Wiring and installation must be in accordance with
applicable electrical codes in accordance with the authority
having jurisdiction.
4. This is a Class A device and intended for commercial or
industrial use. This equipment may cause radio interference
if used in a residential area; in this case it is the operator’s
responsibility to take appropriate measures.
5. The precondition for compliance with EMC limit values
is strict adherence to the guidelines specified in the
SL-MOD-GW User manual. This applies in particular to the
area of grounding and shielding of cables.
FCC Notice (USA only)
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
Industry Canada Notice (Canada only)
This Class A digital apparatus complies with Canadian ICES-003.
DIN rail mounting and removal
2
1
Click
DIN rail
To mount the unit on a DIN rail, slot
the top part of the SL-MOD-GW in-
to the upper guide of the rail and
lower the enclosure until the bot-
tom of the red hook clicks into
place.
Slide down
2
1
To remove the SL-MOD-GW from
the DIN rail, use a screw driver
as a lever by inserting it in the
small slot of the red hook and push
the red hook downwards. Then re-
move the unit from the rail by rais-
ing the bottom front edge of the en-
closure.
Mounting rules
No water splash and water drops
No aggressive gas, steam or liquids
Avoid dusty environments.
Avoid shock or vibration
Do not exceed the specified operational temperatures and
humidity range.
Mount inside an electrical switchboard or control cabinet.
Make sure there is sufficient air ventilation and clearance to
other devices mounted next to the unit.
Observe applicable local regulations like EN60204 /
VDE0113.
Before connecting anything
1. Before installing or removing the unit or any connector,
ensure that the system power and external supplies have
been turned off.
2. Check the system supply voltage with a multimeter for
correct voltage range and polarity.
3. Connect the power supply cable and switch on the system
power. Check if the Power LED is lit.
4. Turn off system power.
5. Connect all I/O cables.
6. Once you are certain that all connections have been made
properly, restore the power.
Power terminals pin assignment
Before connecting power please follow the rules in the section
called “SAFETY PRECAUTIONS” and the section called “Be-
fore connecting anything”.
V+
V-
1
1 V+ Positive voltage supply (10 - 30 V DC)
2 V- Negative voltage supply, DC power return
Make sure that the polarity of the supply voltage is correct
before connecting any device to the serial ports! A wrong
polarity can cause high currents on the ground plane
between the V- power supply pin and the serial port ground
pins, which can cause damage to the device.